paige_irr_spec

P7307D

Download printable PDF version

p7307
INTERLOCKED ARMOR CABLE
600 VOLT UL TYPE MC
INSULATION: (XLP) CROSS-LINKED
POLYETHYLENE
JACKET: SUNLIGHT RESISTANT PVC
SIZES: 14 AWG – 750 MCM, 3 OR 4 CONDUCTOR
90°C WET/DRY


1.0 SCOPE:

1.1 Designed for use as a power cable where maximum protection is required. The cable is UL listed for wet and dry locations and can be used for direct burial and submersible pump applications.


2.0 CONSTRUCTION:

2.1 Conductor:

3 or 4 Class B stranded copper

2.2 Insulation:

Heat and moisture resistant cross-linked polyethylene (type XHHW-2), phase identified.

2.3 Fillers:

When needed

2.4 Ground:

1 bare copper ground for 3 conductor
2 bare copper ground for 4 conductor

2.5 Armor:

Core covered with binder tape, aluminum or galvanized steel interlocked armor

2.6 Jacket:

Flame and sunlight resistant black PVC jacket. (Jacket available under armor and in other colors)

2.7 Color Code:

K-2/ other color codes available

2.8 Temperature:

90ºC Wet/Dry Per ICEA S-66-534/NEMA WC-7

2.9 Cable Reinforcement:

An open reinforcement is applied over the assemble for mechanical protection

2.10 Underwriters’ Laboratories Approval:

All cables shall be tested physically and electrically in accordance with UL and IEEE-383 flame test with additional 210,000 BTU rating. All reels and cartons bear UL labels. CT use – UL approved; UL 1569


Size
AWG
or
MCM
Strand
(NO.)
Insulation
Thickness
(MILS)
Copper
Grounding
Conductor(s)
(AWG)
Diameter
Over
Armor
(INCH)
PVC Jacket
Thickness
(MILS)
Approx.
Diameter
Overall
(INCH)
Aprox. NET WT.
Per 1000 FT. (LBS.)
Ampacity*
(30ºC Ambient Wet/Dry)
90ºC
Aluminum
Armor
Galv.
Armor
THREE CONDUCTOR
14
12
10
8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
7
7
7
7
7
7
7
19
19
19
19
19
37
37
37
61
30
30
30
45
45
45
45
55
55
55
55
55
65
65
65
80
14
12
10
10
8
8
6
6
6
6
4
4
4
3
2
1
.575
.575
.575
.718
.806
.905
1.030
1.270
1.410
1.520
1.630
1.760
1.910
2.140
2.450
2.940
50
50
50
50
50
50
50
50
50
60
60
60
60
60
75
75
.675
.675
.675
.818
.906|
1.010
1.130
1.270
1.410
1.520
1.630
1.760
1.910
2.140
2.450
2.940
200
236
291
405
542
723
1024
1247
1534
1859
2305
2760
3196
4249
6344
9028
297
333
393
530
682
881
1209
1455
1852
2203
2682
3169
3641
4757
6923
9719
25
30
40
55
75
95
130
150
170
195
225
260
290
350
430
535
FOUR CONDUCTOR
14
12
10
8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
7
7
7
7
7
7
7
19
19
19
19
19
37
37
37
61
30
30
30
45
45
45
45
55
55
55
55
55
65
65
65
80
16
14
12
12
10
10
8
8
8
8
6
6
6
4
4
3
.575
.575
.600
.780
.870
.990
1.140
1.330
1.430
1.540
1.670
1.810
1.980
2.230
2.550
3.090
50
50
50
50
50
50
50
60
60
60
60
60
60
75
75
85
.675
.675
.700
.880
.980
1.090
1.240
1.450
1.550
1.660
1.790
1.930
2.100
2.380
2.700
3.260
233
270
349
498
673
914
1326
1675
1990
2376
2911
3510
4076
5889
8072
11670
338
372
455
633
826
1090
1530
2000
2340
2579
3328
3959
4571
6449
8716
12439
20
24
34
44
60
76
104
120
136
156
180
208
232
280
344
428

*Per NEC Table 310-16.
**Fillers when needed.
NOTE: The data shown is approximate and subject to standard industry tolerances.